The IOR12 converts an analogue output of an
BMS controller to two stages of relay output,
and acts as an interface between the controller
and heating, cooling and ventilating equipment.
It may be configured as a high/low or a
raise/lower relay module by link selection. The
raise/lower mode has a stroke time function,
which is implemented by a 16-bits microcontroller.
There are manual override links for
each relay to aid commissioning. Field wiring is
facilitated by rising cage clamp type terminals,
and a supply loop terminal aids wiring to additional
modules. |
| |
| Features |
converts an analogue output signal to two stages of relay output |
| Spec. |
Supply voltage :24Vdc or Vac +/- 20%
Supply current :35mA (24mA for single relay)
@ 24Vac/dc
Input signal :0 to 10Vdc (4mA maximum)
Contacts :240Vac single phase only 5A (
or inductive load, cos¦µ=0.4), and 20Vdc at 5A
(inductive load). For 24Vdc (inductive load) reduce to 2A, Arc suppression recommended.
Operating modes: linkable High/Low Raise/Lower
Manual override: Linkable AUTO/ON/OFF
Led :Single LED for each relay. On energized
Ambient limits:
storage : -10ºC(14 ºF) to +70ºC(158 ºF)
operating : -10ºC(14 ºF) to +50ºC(122 ºF)
humidity :0 to 90%RH non-condensing
|
Order Code
|
| Order code | Description |
| IOR12 | Two relay module |
|
|
|
|