Duct/Space CO2 sensors
   
used for CO2 measurement. The simple structure and reference measurement capabilities make this single beam dual wavelength NDIR sensor extremely stable and reliable. The temperature and flow dependence is negligible and the accuracy is even not affected by dust, water vapor or most chemicals. Flexible output options such as 4-20mA, 0-10V and LonWork interface make it suitable for all HVAC commercial applications.
 
Features Nondispensive Infra Red technology (NDIR)
anlogue output 4-20mA or 0-10V
long term stability
24V ac/dc supply
negligible temperature dependenc
Spec. CO2 measurement range:0 - 2000ppm
accuracy:+/-30ppm+2%reading@25ºC
non-linearity:+/-1%FS
temperature dependence:+/-0.15%FS/ºC
long term stability:<5%FS/5year
power supply:24Vac/Vdc+20%
comsumption:<2.5Watts
recommended load:
I type:max 500 ohm
V type:min 1K ohm
operating temperature:-5ºC - +45ºC
humidity:0-85%RH noncondensing
Order Code
Order Code Description Weight
GSCO21 Room type CO2 sensors 100g
GSCO22 Duct type CO2 sensors 140g
  BACK  