R-type structure, AC V and I input, 4-20mA output, this 3 phase active power transducer adopts high speed digital collection and synchronous data process technology to make V/I conversion responsive thus to precisely measure the active power value. Completely isolated from field signals, this type of transducer can also be used in complicated environment. |
| |
| Features |
compact size
R type structure
4-20mA output |
| Spec. |
accuray: 0.5
input(AC): V<=500V,I<=5A
output(DC):VZ =4 - 20mA
input freq.:50HZ
response time: <300ms
linear range:
V: 20%-125% nominal
I: 1%-125% nominal
C: 0.1(hysteresis)-1 -0.1(leading)
load capacity:6 V
input resistance:RV =VX x 1Kohm/V(VX >=10V)RI ~=0
overload:
voltage 2 x nominal
current 10 x nominal
power supply:R1:+12V/R4:+24V
quiescent consumption:600mw
isolation durability:2500VDC/min
variation:<=+/-0.5%/0~50ºC
voltage range: 240V |
Order Code
|
| Order Code | Class |
| PMP111 | 0.5 |
| PMP112 | 0.2 |
|
|
|
|