| This module is designed for DIN-rail mounting inside AHU's, power distribution units or general areas where leak detection is required. A relay output is available for alarm signaling. |
| |
| Features |
Can be used with cable, point or rain sensors
AC detector excitation for reliability
24Vac/dc or 230Vac versions
Audible alarm option |
| Spec. |
Detection Module
Supply: 24Vac/dc, or 230Vac
Supply current: 50mA max.
Output: SPDT relay 12A @ 230Vac
Response time: <1 sec. after exposure
Max. tape length with netting: 50 metres (with leader cable)
Max. sensor cable length: 200 metres (with leader cable)
Housing: DIN-rail carrier
Dimensions: 77 x 67 x 44mm
Rain Sensor
Heater supply voltage: 24V @ 40mA max.
Dimensions: 70 x 43 x 30mm max.
Weight: 125g
Point Sensor
Dimensions: Body 70 x 43 x 30mm max.
Steel probes 8mm long x 8mm apart
Weight: 125g
Water Cable Sensor
Lengths: 5, 10 or 15 metres
|
Order Code
|
| Order code | Description |
| WD11 | 24Vac/dc,Water detection module |
| WD12 | 24Vac/dc,Water detection module + buzzer |
| WD13 | 230Vac, Water detection module |
| WD14 | 230Vac, Water detection module + buzzer |
| WD21 | Point Water Sensor |
| WD22 | Rain Sensor with integral heater - 1 metre |
| WD23 | Rain Sensor with integral heater - 2 metre |
| WD24 | Rain Sensor with integral heater - 3 metre |
| WD25 | Water Cable Sensor, 5m cable, 3m leader |
| WD26 | Water Cable Sensor, 10m cable, 3m leader |
| WD27 | Water Cable Sensor, 15m cable, 3m leader |
|
|
|
|